Calibration of DAIT (Read 3135 times)
Reply #1 - Oct 26th, 2011 at 5:29am

HavenMade Administrator   Offline
YaBB Administrator
The obvious isn't obvious
until it is obvious
Colorado

Gender: male
Posts: 47
*****
 
Myron; It is good to see you on here.

The full DAIT system consists of sensors by each pump. There are summer sensors and winter sensors. The summer is set to 120 Degrees before it switches on and off at 90 degrees +- 5 degrees.
Winter is 130 and shuts off at 110 degrees.
The sensors should be directly above the pump very close 5 to 8 inches. 
The external sensor is operated by the small circuit board inside the DAIT control box.
It should be set to 80Deg F to switch between summer and winter mode.
The best way to do that is with warm water and a thermometer.  raise the water to 80 degrees.
Place the thermister in a plastic bag and in the water. Adjust the DAIT until the light just goes off.
 

The Administrator.
IP Logged
 
Oct 25th, 2011 at 10:17pm

MyronW   Offline
YaBB Newbies
San Diego County

Gender: male
Posts: 3
*
 
What is the proper procedure for the calibration of the DAIT system?
 